Independent, privacy-first network planning tools
BATTERY BACKUP

UPS runtime estimator

Estimate outage runtime from battery specifications and actual network load, while checking both W and VA ratings.

1. Battery and load

Total number of identical batteries
Conservative factor for age and high discharge

2. Estimate

Estimated runtime
Hours
Estimated usable energy
Recommended minimum
W rating check
VA rating check
Important: This is a simple energy model. Lead-acid batteries deliver less than rated Ah at high loads; temperature, age and UPS cutoff voltage also matter. Prefer the manufacturer runtime curve for a specific model.

Formula

Nominal Wh = V × Ah × battery count
Usable Wh = nominal Wh × inverter efficiency × usable battery factor
Estimated hours = usable Wh ÷ load W

How to separate VA, W and runtime when choosing a UPS →